Product

WSG Position Indicator
GS 80.3 - WSG 90.1 - Product presentation

Product Description

  • Signalling of position and end position of AUMA part-turn gearboxes
  • Continuous mechanical position indication and electrical position feedback
  • For direct coupling with gear worm wheel: precise, low backlash position feedback

Product Spesification

Features and functions
  • Version : Closing direction clockwise, closing direction counterclockwise
  • Swing angle
    Standard: 90° - adjustable within a tolerance range of ±8°;
    Factory setting to 90°, unless another angle is defi ned in the order.
    Options: 34° – 50°, 50° – 66°, 66° – 82°, 98° – 130°, 130° – 180°; adjustable
  • Power supply : 24 V DC +/– 15 % smoothed, max. 80 mA
  • Status signal : Contactless end position switches (Hall sensors) for end positions OPEN and CLOSED
    Standard: 2 potential-free output contacts with one common for signalling end position OPEN,
    end position CLOSED
    Max. 250 V AC, 3 A (resistive load), min. 5 V, 10 mA
    Option: RWG with max. 250 V AC, 3 A (resistive load), min. 5 V, 10 mA
  • Position feedback signal, analogue
    (options)
    Potentiometer: Film potentiometer 5 kΩ/0.5 W/linearity ±0.5 %
    Wire potentiometer 5 kΩ/1.5 W/linearity ±0.5 %
    Position transmitter: Electronic position transmitter RWG:
    0/4 – 20 mA in 3 or 4-wire version
    4 – 20 mA in 2-wire version
    Technical data RWG
    3-wire or 4-wire system 2-wire system
    Output current Ia 0 – 20 mA, 4 – 20 mA 4 – 20 mA
    Power supply UV 24 V DC (18 – 32 V) 14 V DC + (I x RB
    ),
    max. 30 V
    Max. current
    consumption
    I 24 mA at 20 mA output current 20 mA
    Max. load RB 600 Ω (UV - 14 V)/20 mA
  • Mechanical position indicator
    Standard: Continuous indication
    Option: Adjustable indicator disc with symbols OPEN and CLOSED
  • Heater in switch compartment: Self-regulating PTC heater; 0 – 20 W; 110 – 250 V AC/DC or 24 – 48 V AC/DC
  • Electrical connection: AUMA plug/socket connector with crimp connection
  • Threads for cable entries
    Standard: Metric threads
    Options: Pg-threads, NPT-threads, G-threads
  • Terminal plan: APG AP301 (basic version)